Prominent & Leading Wholesale Trader from Ahmedabad, we offer ats-01 automatic transfer controller.
₹ 3,000 /Piece Get Latest Price
Model Name/Number | ATS-01 |
Weight | 1100 g +/- 2% |
Operating Temperature | -20 Degree Celcius ~ 70 Degree Celcius |
Frequency Measurement Range | 45HZ to 70Hz |
Generator Start Relay | 7Amp @ 250VAC Max |
Transfer to Normal Relay | 7Amp @ 250VAC Max |
Input Control Voltage | 160 VAC to 260 VAC 50/60 Hz |
Operating Humidity | 0 to 95% relative humidity |
Voltage Measurement Range | 80 VAC to 550 VAC 50/60 Hz |
Storage Temperature | -35 Degree Celcius ~ 85 Degree Celcius |
Auxiliary Relay | 0.5Amp @ 120VAC 1.0Amp @ 24VDC |
Transfer to Standby Relay | 7Amp @ 250VAC Max |
Country of Origin | Made in India |
Minimum order quantity: 5 Piece
Preliminary Comments and Safety Precautions
This technical document is intended to cover most aspects associated with the installation, application, operation and maintenance of the ATS-01 Automatic Transfer Switch Controller. It is provided as a guide for authorized and qualified personnel application of the ATS-01 Automatic Transfer Switch Controller.
Overview
Transfer switches are used to protect critical electrical loads against loss of power. The load''''''''''''''''s normal power source is backed up by a standby (emergency) power source. A transfer switch is connected to both the normal and emergency sources and supplies the load with power from one of these two sources. In the event that power is lost from the normal source, the transfer switch transfers the load to the standby source. Once normal power is restored, the load was transferred back to the normal power source.
Product Overview
The ATS-01 Automatic Transfer Switch control module is an intelligence, comprehensive, multi-function, microprocessor based automatic transfer switch controller. It is a compact panel mounted device designed to replace traditional relay and solid state logic panels and meet the needs of markets worldwide. The ATS-01 controller provides an unmatched degree of programmed flexibility to address the needs of most switches system. It can be programmed for 3Ø, 1Ø and 1Ø 3W system operation. ( Refer to program line 2 ) The ATS-01 controller provides the necessary intelligence to insure that the switch operates properly through a series of programmed sensing and timing functions. The ATS-01 controller will :
Monitor Normal and Standby source over and
under voltages.
Monitor Normal and Standby source over and
under frequencies.
Permit customer programming display real time
information.
Permit customer programming cyclic mode or fix
mode display for 3 phase voltages and frequency.
( Refer to program line 29 )
Permit system testing the transfer switch
with/without load from front panel. ( Refer to
program line 4 )
Store customer / factory established parameters
in memory without losing
Feature 1 :Time Delay Normal to Emergency(TDNE)TDNE provides a time delay when transferring theNormal source to the Standby source. It ensuresstability of the Standby source. Timing begins whenthe Standby Source becomes available. ( Refer toprogram line 6 )Adjustable TDNE range : 0 ~ 60 (0 ~ 300 sec)Feature 2 : Time Delay Engine Start (TDES)TDES delays the initiation of the engine start circuitin order to override momentary power outages orvoltage fluctuations of the Normal source. TheTDES timer shall start when the Normal sourcebecomes unavailable. If the Normal sourcebecomes available while timing, the TDES timer willreset. The ATS-01 controller can perform the timedelay engine start function without control power for30 seconds. ( Refer to program line 7 )